StructureÂ
Â
Standard for 300mm2 XLPE cableÂ
Hongda 300mm2 XLPE cable is manufactured according to the standard of GB12706 or IEC,BS,DIN and ICEA upon request.
Â
Applications for 300mm2 XLPE cableÂ
XLPE cable is suitable for dynamic line transmission and distribution lines of shielding performance requirements more stringent,especially applies to the rated voltage 0.6/1kV and below frequency inverter control system for power supply or connectiing cables.Frequency conversion cable is actually a shield-type power cable,the difference is that ground wires are divided into third part placed in the three main line between core to uniform electric field and improve levels of electromagnetic radiation of cable.Mostly used in high-power inverter power supply and frequency conversion motor connection
Â
Operating characteristics for 300mm2 XLPE cable
1.Rated power-frequency voltage Uo/U of electrical cable : 0.6/1kV
2.Max.permissible continuous operating temperature of electrical cable conductor: 90°C
3.Max.short-circuit temperature of electrical cable conductor shall not exceed 250°C.(5s maximum)
4.The ambient temperature under installation should not below 0°C
5.The bending radius of electrical cable should not less than 15 times of electrical cable diameter.
Â
The type of 300mm2 XLPE cable
Chinese Type |
Description of xlpe insulated cable |
Core qty |
Conductors range |
YJV |
Copper conductor, xlpe insulated cable, PVC outer sheath Power Cable |
1, Â 2, Â 3, Â 4, 3+1, 5, Â 4+1, 3+2 |
1.5~800mm2 |
YJY |
Copper conductor, XLPE insulated cable, PE outer sheath Power Cable |
1, Â 2, Â 3, Â 4, 3+1, 5, Â 4+1, 3+2 |
1.5~800mm2 |
ZA-YJV ZB-YJV ZC-YJV |
Copper conductor, XLPE insulated flame-retardant Power Cable |
1, Â 2, Â 3, Â 4, 3+1, 5, Â 4+1, 3+2 |
1.5~800mm2 |
WDZA-YJY WDZB-YJY WDZC-YJY |
Copper conductor, XLPE insulated cable of Low Smoke Halogen Free or Zero Halogen (LSHF or LSZH) flame-retardant Power Cable |
1, Â 2, Â 3, Â 4, 3+1, 5, Â 4+1, 3+2 |
1.5~800mm2 |
NH-YJV |
Copper conductor, XLPE insulated cable of fire-resistant Power Cable |
1, Â 2, Â 3, Â 4, 3+1, 5, Â 4+1, 3+2 |
1.5~800m |

Â
DIMENSIONS | |||||||||
Cores number N° |
Cross section mm² |
Approx conductor diameter mm |
Insulation medium thickness mm |
Min. sheath thickness mm |
Max. external diameter mm |
Electric resistance at 20°C ohm/km |
Approx cable weight kg/km |
Current carrying air free A |
Current carrying burried A |
Single core | |||||||||
1x | 1.5 | 1.4 | 0.7 | 1.09 | 6.6 | 12.1 | 45 | 24 | 31 |
1x | 2.5 | 1.8 | 0.7 | 1.09 | 7 | 7.41 | 55 | 33 | 41 |
1x | 4 | 2.25 | 0.7 | 1.09 | 7.6 | 4.61 | 75 | 45 | 59 |
1x | 6 | 3.05 | 0.7 | 1.09 | 8.2 | 3.08 | 100 | 58 | 74 |
1x | 10 | 3.8 | 0.7 | 1.09 | 9.2 | 1.83 | 140 | 80 | 101 |
1x | 16 | 4.7 | 0.7 | 1.09 | 10.5 | 1.15 | 205 | 107 | 128 |
1x | 25 | 5.9 | 0.9 | 1.09 | 12.5 | 0.727 | 315 | 138 | 144 |
1x | 35 | 7.1 | 0.9 | 1.09 | 13.5 | 0.524 | 400 | 169 | 174 |
1x | 50 | 8 | 1 | 1.09 | 15 | 0.387 | 530 | 207 | 206 |
1x | 70 | 9.6 | 1.1 | 1.09 | 17 | 0.268 | 725 | 268 | 254 |
1x | 95 | 11.4 | 1.1 | 1.18 | 19 | 0.193 | 985 | 328 | 301 |
1x | 120 | 13.1 | 1.2 | 1.18 | 21 | 0.153 | 1260 | 382 | 343 |
1x | 150 | 14.6 | 1.4 | 1.26 | 23 | 0.124 | 1520 | 441 | 387 |
1x | 185 | 16.5 | 1.6 | 1.26 | 25.5 | 0.0991 | 1940 | 506 | 434 |
1x | 240 | 18.4 | 1.7 | 1.35 | 28.5 | 0.0754 | 2310 | 599 | 501 |
1x | 300 | 21.1 | 1.8 | 1.43 | 31 | 0.0601 | 3200 | 693 | 565 |
1x | 400 | 23.5 | 2 | 1.52 | 34.2 | 0.047 | 3931 | - | 639 |
1x | 500 | 26.5 | 2.2 | 1.6 | 38 | 0.0366 | 5020 | - | 713 |
1x | 630 | 30.1 | 2.4 | 1.69 | 44 | 0.0286 | 5324 | - | 785 |
Two cores | |||||||||
2x | 1.5 | 1.4 | 0.7 | 1.43 | 10.5 | 12.1 | 115 | 26 | 37 |
2x | 2.5 | 1.8 | 0.7 | 1.43 | 11.5 | 7.41 | 145 | 36 | 48 |
2x | 4 | 2.25 | 0.7 | 1.43 | 13 | 4.61 | 195 | 49 | 63 |
2x | 6 | 3.05 | 0.7 | 1.43 | 14 | 3.08 | 265 | 63 | 80 |
2x | 10 | 3.8 | 0.7 | 1.43 | 16 | 1.83 | 390 | 86 | 104 |
2x | 16 | 4.7 | 0.7 | 1.43 | 18.5 | 1.15 | 560 | 115 | 136 |
2x | 25 | 5.9 | 0.9 | 1.43 | 22 | 0.727 | 850 | 149 | 173 |
2x | 35 | 7.1 | 0.9 | 1.43 | 24.5 | 0.524 | 1080 | 185 | 208 |
Three cores |